FROR PVC Control Cable
Application of FROR Wire
These high-quality cables are insulated with standard and approval-quality PVC, and are sheathed in heavy-duty PVC. They are suitable for connections and movable equipment, even in places of public entertainment. They can be installed inside, in dry or humid environments (AD2), and for temporary use outside, provided they are not permitted under the laying plaster or underground, even if they are protected.
Construction of FROR Cable
Fine bare copper strands
Strands to IEC 60228 class 5
PVC core insulation TI2 to CEI 20-11
Color codes to Unel 00722
Green-yellow grounding, 3 conductors and above
PVC outer jacket TM 2 - Black (RAL 9005), Gray(RAL7001/7035)
Technical Characteristics
Working Voltage | 300/500 volts, 450/750 volts |
Test voltage | 2500 volts |
Flexing bending radius | 10 x Ø |
Static bending radius | 4 x Ø |
Flexing Temperature | -15°C to +70°C |
Fixed Temperature | 0°C to +70°C |
Short-circuit temperature | 160 °C |
Flame retardant | CEI 20-22 II |
Insulation resistance | 20 MΩ x km |
Technical Parameter of FROR Control Wire
Cable Parameter | |||||
AWG | No. of Cores x Nominal Cross Sectional Area | Nominal Thickness of Insulation | Nominal Thickness of Sheath | Nominal Overall Diameter | Nominal Weight |
mm2 | mm | mm | mm | kg/km | |
FROR 300/500V | |||||
18(24/32) | 7 x 1 | 0.6 | 1 | 11.2 | 153 |
18(24/32) | 10 x 1 | 0.6 | 1.2 | 14.4 | 222 |
18(24/32) | 12 x 1 | 0.6 | 1.2 | 14.9 | 252 |
18(24/32) | 16 x 1 | 0.6 | 1.3 | 16.6 | 332 |
18(24/32) | 19 x 1 | 0.6 | 1.4 | 17.8 | 387 |
18(24/32) | 24 x 1 | 0.6 | 1.5 | 20.8 | 487 |
18(24/32) | 27 x 1 | 0.6 | 1.6 | 21.5 | 602 |
16(30/30) | 7 x 1.5 | 0.7 | 1.2 | 13.2 | 217 |
16(30/30) | 10 x 1.5 | 0.7 | 1.3 | 16.8 | 307 |
16(30/30) | 12 x 1.5 | 0.7 | 1.4 | 17.6 | 347 |
16(30/30) | 16 x 1.5 | 0.7 | 1.5 | 19.5 | 457 |
16(30/30) | 19 x 1.5 | 0.7 | 1.6 | 20.6 | 522 |
16(30/30) | 24 x 1.5 | 0.7 | 1.7 | 24.4 | 677 |
16(30/30) | 27 x 1.5 | 0.7 | 1.8 | 25.1 | 722 |
FROR 450/750V | |||||
18(24/32) | 2 x 1 | 0,7 | 1 | 8.8 | 76 |
18(24/32) | 3 x 1 | 0,7 | 1,0 | 9.2 | 90 |
18(24/32) | 4 x 1 | 0,7 | 1 | 9.8 | 107 |
18(24/32) | 5 x 1 | 0,7 | 1,1 | 11.2 | 137 |
16(30/30) | 2 x 1.5 | 0,7 | 1,0 | 9.3 | 91 |
16(30/30) | 3 x 1.5 | 0,7 | 1,0 | 9.7 | 110 |
16(30/30) | 4 x 1.5 | 0,7 | 1,1 | 10.8 | 135 |
16(30/30) | 5 x 1.5 | 0,7 | 1,2 | 11.9 | 169 |
14(50/30) | 2 x 2.5 | 0,8 | 1,2 | 11.3 | 136 |
14(50/30) | 3 x 2.5 | 0,8 | 1,2 | 11.8 | 165 |
14(50/30) | 4 x 2.5 | 0,8 | 1,2 | 12.8 | 202 |
14(50/30) | 5 x 2.5 | 0,8 | 1,3 | 14.2 | 254 |
12(56/28) | 2 x 4 | 0,8 | 1,2 | 12.6 | 180 |
12(56/28) | 3 x 4 | 0,8 | 1,3 | 13.4 | 229 |
12(56/28) | 4 x 4 | 0,8 | 1,3 | 14.6 | 280 |
12(56/28) | 5 x 4 | 0,8 | 1,5 | 16.4 | 353 |
10(84/28) | 2 x 6 | 0,8 | 1,3 | 13.8 | 244 |
10(84/28) | 3 x 6 | 0,8 | 1,4 | 14.8 | 307 |
10(84/28) | 4 x 6 | 0,8 | 1,4 | 16.2 | 377 |
10(84/28) | 5 x 6 | 0,8 | 1,5 | 18 | 478 |
About FROR Cable
This cable is employed by prominent corporations (FIAT, COMAU, etc.) for measurement and control purposes in machine tools and conveyors, as well as on production lines in equipment production and for special mechanical engineering. These cables are characterised by their versatility, accommodating medium mechanical stresses with unrestrained movement without tensile stress or forced movements in dry, moist and wet rooms, though not in open air. The cable's flame resistance, attributable to its special conductor insulation and jacket compound, is notable. In the event of a fire, the cable is self-extinguishing. Its oil- and petrol-resistance is also a noteworthy attribute, allowing for its use in challenging environments.